Overview
The AL400ULX power supply
converts a 115VAC / 60Hz input, to a
4 amp of continuous supply current @
12VDC or 3 amp of continuous supply
current at 24VDC power limited
output, (see specifications).
Specifications:
Agency listings:
• UL Listed for Access Control Systems (UL294),
Burglar Alarm Systems (UL603),
Hospital Signaling and Nurse Call Equipment (UL1069),
Power Supply for Fire Protective Signaling and Systems (UL1481)
CUL Listed - CSA Standard C22.2 No.205-M1983, Signal Equipment
File # S4707.
• CSFM - California State Fire Marshal Approved.
File # 7315-1335:100.
MEA - NYC Department of Buildings Approved.
File # 120-93-E.
• FM approved.
• NFPA 72 compliant.
Input:
• 115VAC / 60Hz, 1.45 amp.
• AC input and DC output LED indicators.
Output:
• Class 2 rated power limited output.
• 12VDC or 24VDC selectable output.
• 4 amp continuous supply current @ 12VDC or 3 amp
continuous supply current at 24VDC.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• Maximum charge current .7 amp.
• Zero voltage drop when switched over to battery backup.
Supervision:
• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).
• Battery presence supervision (form "C" contacts).
Additional Features:
• Power supply, enclosure, cam lock and battery leads.
• All models are available in red enclosure
(add an "R" suffix to the part # e.g. AL400ULXR).
Enclosure Dimensions: 13”H x 13.5”W x 3.25”D